  General use of many types of condenser is both vertical and horizontal, these two devices are simple contrast;
  Horizontal and vertical condenser both different placement and allocation of water, the water temperature rise and water consumption are not the same. The vertical condenser cooling water is along the gravity along the inner wall of the tube downstream, only a single stroke, so to obtain a sufficiently large heat transfer coefficient K, a large amount of water must be used.
  Horizontal condenser pump Cooling water supplied to the cooling pipe, it can be made multi-line program condenser, and the cooling water can be sufficiently large flow rate and the temperature rise (ΔT = 4 to 6 ° C). Horizontal condenser with a small amount of cooling water can be obtained sufficiently large K values​​.
  But excessively increase the flow rate, the heat transfer coefficient K value increases no more than, and the power consumption of the cooling water pump is increased significantly, so ammonia horizontal condenser of the cooling water flow rate and generally preferably about 1m / s, a freon horizontal condensation Most of the cooling water flow rate is 1.5 ~ 2m / s.